FLUKE 1587 ET
Advanced Electrical Troubleshooting Kit
The products in this kit have been specifically selected for both troubleshooting and preventative maintenance applications.
General
Establishing preventative maintenance programs are becoming critical to maintaining the uptime of electrical equipment and can significantly reduce both planned and unplanned downtime. Unplanned downtime costs are difficult to calculate, but often significant. For some industries, it can represent 1% - 3% of revenue (potentially 30% - 40% of profits) annually.
Includes a Fluke 1587 Insulation Multimeter, Fluke i400 Current Clamp, and a Fluke 62 Mini Infrared Thermometer.
- With the Fluke 1587, perform insulation tests, plus a wide-range of DMM tasks with confidence and ease.
- Use the Fluke i400 with your Fluke 1587 to accurately measure AC current without breaking the circuit.
- Check for hot spots and measure temperature with the Fluke 62 Mini non-contact thermometer.
Fluke 1587 Insulation Multimeter
- With the Fluke 1587, perform insulation tests, plus a wide-range of DMM tasks with confidence and ease.
- Two products in one: Powerful and full-featured multimeter.
- Ideal for work on motors, cables, and switch gear.
- Large display with backlight.
- Filter for motor drive measurements.
- Insulation test (0.01 MΩ to 2 GΩ).
- Insulation test voltages (50 V, 100 V, 250 V, 500 V, 1000 V) for many applications.
- CAT III 1000 V /CAT IV 600 V overvoltage rating for added user protection.
Fluke i400 Current Clamp
- Use the Fluke i400 with your Fluke 1587 to accurately measure AC current without breaking the circuit.
- Use with your Fluke 1587 to measure 1A AC to 400 A AC.
- 1 mA/Amp output guarantees easy reading.
- CAT III 1000 V / CAT IV 600 V overvoltage rating for added user protection.
- Specially designed to offer maximum utility in a very compact shape.
- Maximum conductor: Ø 32 mm.
Fluke 62 MAX+ IR Thermometer
- Dust and water-resistant: IP54 rated.
- Rugged: 3-meter (9.8-foot) drop tested.
- Ergonomically designed: Completely redesigned for a more natural hand fit.
- Distance to spot: 12:1.
- Dual lasers: Identifies area to be measured.
- Large, backlit display: Makes data easier to read, even in dark areas.
Specifications
Fluke 1587 Insulation Multimeters
Specifications | ||
Voltage DC | Maximum voltage | 1000 V |
Accuracy | ±(0.09% + 2) | |
Maximum resolution | 0.001V | |
Voltage AC | Maximum voltage | 1000 V |
Accuracy | ±(2% + 3) | |
AC Bandwidth | 5kHz (with low pass filter; 3 db @ 800 Hz) |
|
Maximum resolution | 0.1 mV | |
Current DC | Maximum amps | 400 mA |
Amps accuracy | ±(0.2% + 2) | |
Maximum resolution | 0.001 mA | |
Current AC | Maximum amps | 400 mA |
Amps Accuracy | ±(1.5% + 2) (1 kHz bandwidth) |
|
Maximum resolution | 0.01 mA | |
Resistance | Maximum resistance | 50 MΩ |
Accuracy | ±(0.9% + 2) | |
Maximum resolution | 0.1 Ω | |
Capacitance | Maximum capacitance | 9,999 µF |
Accuracy | ±(1.2% + 2) | |
Maximum resolution | 1 nF | |
Temperature measurement | -40.0°C to 537°C -40.0°F to 998°F excluding probe |
|
Diode test | Range | 6 V |
Resolution | 1 mV | |
Accuracy | ±(2% + 1) | |
Insulation Test | ||
Minimum test current @ 1 kΩ/V | 1 mA | |
Test voltages | 50, 100, 250, 500, 1000 V | |
Maximum resistance per test voltage | 50 V | |
100 V | ||
250 V | ||
500 V | ||
1000 V | 2 GΩ | |
Maximum resolution per test voltage | 50 V | 2 GΩ |
100 V | 0.01 MΩ | |
250 V | 0.1 MΩ | |
500 V | 0.1 MΩ | |
1000 V | 0.1 MΩ | |
Accuracy per test voltage | 50 V | ±(3% + 5) |
100 V | ±(3% + 5) | |
250 V | ±(1.5% + 5) | |
500 V | ±(1.5% + 5) | |
1000 V | ±(1.5% + 5) to 600 MΩ, ±(10% + 3) above 600 MΩ |